Generalization Testing of Grid Foundation Models for Power Flow and Optimal Power Flow
Ayushi Jolotia, Parikshit Pareek · 14 Nov 2026 · arXiv
Abstract
There is growing interest in foundation models (FMs) for power grids, particularly for power flow and optimal power flow. Their usefulness depends on generalization accuracy, which existing works test on their own benchmarks. We propose a three-axis framework to test their generalization limits: changed admittance matrices of training grids, load levels, and unseen grids. We test GENCO, LUMINA and GridSFM against the DC baseline, alongside their reported limitations, and discuss theoretical reasons for their failures. Experiments reveal that adding a line degrades all FMs more than removing one, and longer lines eventually make LUMINA and fine-tuned GENCO worse than DC. All three degrade beyond their training load range, where the loading-voltage curve steepens. On unseen grids, LUMINA degrades sharply even inside its training range, and GridSFM fails on the grid farthest from it. Thus, beyond training conditions, FMs behave more like meta-models requiring test-time fine-tuning data and compute.
Comments
No comments yet. Share your own experience below.
Visitor posts are moderated before they appear and are the opinion of their authors, not DEEKOYA AI. Names are not verified. See our privacy policy.